Clean room engineering test environment: performance test meets environmental requirements;

What are the acceptance method air shower | air shower equipment

Temperature: 5~35℃;


Relative humidity: 35%~85%;


Power supply: power supply voltage deviation: ±10% of rated voltage;


Power supply frequency deviation: ±2Hz



Test instrument for purification workshop: it shall be verified by the testing institution on a regular basis and put into use only after the calibration is qualified, and it shall be used within the specified validity period;


The following instruments are required for the test:


a) Hot ball anemometer, measuring error ≤±3% full scale;


b) Particle counter;


c) Illuminometer, measuring range is 0lx ~1000lx;


d) Sound level meter, measuring range should be 40 dB~100dB;


e) Ground resistance tester;


f) Leakage current measuring instrument;


g) Voltage tester, output 50Hz, basic sine wave 1500V voltage, and duration within one minute.